FSoE — functional safety
FSoE (Safety over EtherCAT) targets functional safety applications; the protocol targets SIL3/PLe (IEC 61508). This product does not claim SIL3/PLe/TÜV certification, and FSoE is not a PLC capability.
Feature overview
| Capability | Description |
|---|---|
| Safety connection setup | Enter ConnId, SafetyAddress and WatchdogTimeMs to establish a safety connection |
| ConnId uniqueness check | Validated in real time as you type; a duplicate raises a red warning immediately |
| State machine visualization | The six states Reset / Session / Connection / Parameter / Data / Failsafe are highlighted in real time |
| CRC error statistics | Running count of CRC check failures |
| Failsafe counter | Count of Failsafe triggers, for tracing site anomalies |
| Failsafe output configuration | Default safe output values sent when communication is interrupted |
FSoE is part of the export by default — like PDOs, it is included in the generated code whenever the slave supports it, with nothing to tick by hand. The safety PDO structs are generated together with the ordinary PDO structs. (This is code generation behaviour; at runtime the safety connection still has to be established explicitly from its connection parameters — it is not exchanged automatically every cycle.)
Quick start
- Connect a slave that supports FSoE to the network and confirm that the GUI detects the FSoE capability automatically
- Open the FSoE tab in the configuration tool
- Enter a unique connection ID in the ConnId field (a duplicate raises a red warning)
- Enter the slave's safety address in the SafetyAddress field (it must match the safety address preset in the slave EEPROM)
- Enter the safety watchdog time in the WatchdogTimeMs field (100 ms is typical)
- Configure the failsafe outputs (the defaults used when communication is interrupted, for example all zero)
- Start the master and watch the safety state machine in the state machine panel move through Reset → Session → Connection → Parameter → Data in order
- Once it reaches Data, the safety input/output data (including the CRC check field) can be observed in the PDO tab
The six states of the safety state machine
The GUI highlights the current state in real time; the active state blinks.
Error statistics and failsafe
The CRC error statistics and the failsafe counter refresh in real time in the status bar at the top of the FSoE tab:
- CRC errors — the cumulative number of frames that failed the CRC check
- Failsafe count — the cumulative number of times the Failsafe state was triggered
If the values keep climbing → check the site wiring, shielding and grounding, and look for electromagnetic interference.
Failsafe outputs
When communication is interrupted or the safety state leaves Data, the master sends the configured failsafe output values to the slave.
In the failsafe outputs panel:
- Enter the default value each safety output takes during an interruption, bit- or byte-wise
- Typical configuration: all outputs set to zero (emergency-stop state)
- Write the values to the master after configuring; they take effect on start